New HIDS Drum Scales!
Click Here to Learn More!On the Hardy modules, which include the HI 1746WS, HI 1756WS, HI 1756-2WS, HI 1769WS and the HI 1769-2WS, the STATUSWORD is a combination of bits giving the condition of the module at that time. Status Fault on bit 6 (value 64) is an indication that the scale is in motion. This will show up as bit 6 in the STATUSWORD being turned on, or if a return status for a command is being returned as 64.
This is not actually an error, it is a condition that either the weight is changing on the scale or the motion tolerance setting is lower than the amount of fluctuation being seen at that time.
To correct this problem, you could increase the motion tolerance setting. Once your Hardy instrument is no longer indicating an "in motion condition" you should be able to set up and calibrate the module. When setting the motion tolerance ensure that you are setting it based on the METRIC setting for the correct format (either float or integer).
This is not an error and getting this indication is not normally something that would require the module to be replaced or returned for repair.