Click Here to Learn More!Some of the older Ethernet IP modules in the control logix system have a link between the TCP connection and the associated CIP connection. If the TCP connection were closed, it would then also close the CIP connection.
The Hardy HI 6600 unot closes the TCP connection used to initially configure the table exchanges when it has completed configuring the table exchanges (CIP connection). This is a common practice in devices; however, when the Ethernet Module closed the TCP connection , it also closed the CIP connection. This caused the communications to be dropped between the Hardy module and the PLC.
Updating the firmware in the Ethernet Module has been found to correct this issue.
Please see attached Technical Note for more detailed information.