- des
- Batching & Blending
- Filling, Dispensing & Dosing
- Product Inspection
- Weighing in Hazardous Areas
- Other Solutions
- Connectivity Options
New HIDS Drum Scales!
Click Here to Learn More!How do I adjust the analog out on my HI 3030?
Configuring the Analog Card Option from the Web Page
Step 1. From the Home Page, click on Configuration. The Configuration Page appears.
Step 2. Click on Options. The Options Page appears.
Step 3. Click on Analog Channel Configuration (Slot _). The Analog Channel Configuration (Slot _) page appears.
NOTE: Both the Voltage Low/High and Current Low/High Outputs are set to default values. 0-10 Volts and 4-20 mA. Output modes are selectable using the Channel Mode menu selection. If you don't want to change the milli Amp (mA) or Voltage (V) Output values, start with the Input Low and Input High (weight) values for your application. Repeat for other channel.
Step 4. For assistance in configuring the Analog Output Card you can click on 'HELP" at the top of the page.
Step 5. Slot 0 indicates that there is an Analog Card installed in the lower option slot location. If the Analog Card is installed in the upper option slot location, it reads Slot 1. The card channels are numbered 0 & 1 for the analog card regardless of which slot it is in.
Step 6. To Configure Channel 0 (mA), Select the Output level in the Chan 0 OUTPUT LOW Text Field and highlight the entire number.
•Type in the mA value in you want for your "Output Low".
•Highlight the number in the "Output High" field.
•Type in the mA value you want for your Output High.
•Highlight the number in the Input Low (weight) field.
•Type in the weight v