Click Here to Learn More!Clearing memory on the HI 1771 WS module will return all the parameters, including calibration, to the factory default settings. The simple procedure for doing this is:
Within the block write buffer, place a decimal value "9999" into the WaverSaver setting, and the value "7321" into the Weight Modes setting. Once this is done, trigger the block write. This will cause the module to reset itself and you should be able to notice the led's on the module acting as they do on a power up. Change these two values back to their original settings to prevent clearing memory again at the first write.
If you use either the C2® calibration or Soft Calibration you will need to enter the "Sticker Value" back into the module. This is done by placing the "Sticker Value", (six digit number on label on the back edge of the board) into the Motion Tolerance location in the write buffer, place a "9999" into the WaverSaver location and "8321" in the Weight Modes location. Trigger the write block. Reset above values back to normal. You can now proceed with the C2® or Soft calibration.