Click Here to Learn More!I want to do C2® calibration with a HI 200DNWM while having live weight in the vessel. How do I tell the system what the live weight is as a reference?
There are two different versions of the HI 200DNWM (Device Net Weigh Module) module, Series A and Series B.
NOTE: Series A modules will not be marked as a Series A. If a module is not labeled Series B, then it is a Series A.
C2® calibration on a Series A HI 200DNWM uses zero for the reference point. There is no way to give it a different reference point. Any time a C2® calibration is done the module assumes an empty scale.
C2® calibration on a Series B HI 200DNWM uses the Calibration Low Weight for the reference point. This allows you to use a value other than zero for the reference point. In this instance, you would set the Cal Low Weight value to the amount of live weight you have in your vessel.