Can I calibrate and configure one channel on my HI 3030-4S without affecting the other three channels?

Last updated 08/11/2014 09:15 AM

Question

My HI 3030 4 channel controller is using remote I/O with four scales connected to it. Can I calibrate and configure one channel without affecting the remote I/O data being sent to my PLC from the other three channels?

Answer

The HI 3030-4S is four independent weight controllers in a single enclosure sharing a power supply, keypad, and display screen. The calibration of one channel of the HI 3030-4S does not affect the other three channels in the unit. The data from each channel that is "mapped" to the RIO communications table is also independent from other data. So calibration of one channel will not have any effect on the data being transferred from another channel. Only the weight reading for the channel being calibrated will be affected.