Can you configure the inputs to be 120 VAC on the HI 3010 or HI 3030?

Last updated 10-14-2014 09:50

Question

On the HI 3030 or HI 3010, is there any way to configure the input ports to be 120 VAC?

Answer

NO, The 5 input ports on the HI 3010 and the HI 3030 are activated only by contacting the input to the ground terminal. If you require this input to be activated by a 120 VAC signal, a separate relay will be required. Utilize a normally open dry contact on the 120 vac relay to make the input to ground connection. The distance from the input connection to the relay must be under 2 meters, use shielded twisted pairs and route the cable away from other high voltage cables.