Cliquez ici pour en savoir plus !The Ethernet I/P option in your HI 4050 or HI 4060 is designed to be able to communicate with the SLC 5/05 or PLC5E processors, and the Micrologix 1100 & Micrologix 1400 Ethernet ports are functionally equivalent, so you can communicate with these processors as well.
See attached tech notes for instructions on how to do this.
One of the tech notes attached, show how to set up the MSG instructions.
For the MSG instructions the starting address for our internal data tables is N7:0 for the read target device settings.
The attached currently shows the MSG20:1 target device Data Table address as N7:10 for the write table. The target device Write table data should start at N11:0
The example of code being used in the 1400 system was sent as an example of communications from the Micro 1400 to the unit. We have supplied this with their permission.