Cliquez ici pour en savoir plus !The Integrated Technician (IT) data available over the Profibus, RIO, or Serial connection from the HI 2151/30WC is limited to the Excitation Monitor.
The status is available over Profibus by doing a block read #37. This will give you the status of the Excitation monitor being ON/OFF and if the monitor is in error or not.
The status available over Remote I/O is as follows:
Block Read Number 12: Integrated Technician Status
Word 0
Bits 0-7 Command Number: A value of 12 (decimal)
Bits 8-15 Reserved for future use
Word 1
Bits 0-7 Excitation Monitor On/Off
Bits 8-15 Excitation Monitor Error/OK
Total Number of Words 2
The “IT” serial command is X E. The possible results are:
OKK - No Errors Detected
ERR - Error Detected
OFF - IT Not Turned On
You can access the full IT data using the front panel display.